Safguard 1100M Low Water Cut-Off w/ Manual Reset & Test Button/Light, 24V
Hydrolevel Safgard 1100M is a compact, commercial-grade 24V low water cut-off (LWCO) with test/manual reset button and labeled wiring harness. This control is designed to interrupt power immediately in a low water condition. Requires manual reset to restart burner when water level is back to normal. Test button allows for a burner circuit to be tested without lowering the water level in a system.

Technical Specifications:
  • System Type: Gas-Fired Hot Water Boilers, Commercial or Residential
  • Reset: Manual
  • Connection: 3/4" NPT
  • Electrical Specs: 24V, 60 Hz, 1 VA (Power Consumption), SPST (Relay Type), NEMA 1 Enclosure
  • Switching Capacity: 50 VA
  • Max Pressure: 160 psi
  • Max Water Temperature: 250°F


Features:
  • Meets ASME CSD-1 requirements for use with commercial water boilers
  • Test button for easy diagnostics without lowering the water level or removing the probe
  • Manual reset with nuisance lock-out protection (does not trip due to power failures)
  • Includes labeled wire harness for easy connection
  • Power, low water, and service-needed LED indicators
  • Standard 4-pin rectangular Molex connector (to LWCO)
  • Compact size and heavy-duty construction
  • Suitable for wiring to 24VAC transformer, Honeywell R8285 control center (or equivalent) or Honeywell L8148E / L8124E aquastats

Write a review

Please login or register to review

Safguard 1100M Low Water Cut-Off w/ Manual Reset & Test Button/Light, 24V

  • Views: 57
  • Brand: Hydrolevel
  • Model: Safgard 1100M
  • MPN: 45-1100M
  • Availability: In Stock
  • Usually ships: within 1 business day(s)
  • $ 114.95

Tags: Safguard 1100M Low Water Cut-Off w/ Manual Reset & Test Button/Light, 24V, Low Water Cut-Off, Manual Reset, Test Button, 24V Water Control, Boiler Safety, Steam Boiler Control, Water Level Monitoring, Industrial Boiler Protection, Safguard 1100M, Test Light, Boiler Protection System, Water Feeder Control